Copper testing
| Certification Testing | TIA 568-C.2 CAT5e, 6, 6A, draft CAT8 |
| Max cable length for dual ended autotest | 500m |
| Insertion Cycles | Channel: 10,000 typical |
| Testparameters | As specified in TIA 1152, IEC 61935-1 |
| Wiremap | |
| Loop Resistance | 0 to 40 ?, ±0.1 ? |
| Length | 0 to 500m, ±0.5m (dual ended testing) |
| Propagation Delay and Delay Skew | 0 to 5000 ns, ±1 ns |
| Attenuation | 0 to 70 dB, ±0.1dB |
| Pair-to-Pair and Power-Sum NEXT | 0 to 85 dB, ±0.2 dB |
| Pair-to-Pair and Power-Sum ACRF | 0 to 85 dB, ±0.2 dB |
| Return Loss | 0 to 40 dB, ±0.2 dB |
| ACRN, PSACRN | 0 to 85 dB, ±0.5 dB |
| Advanced Diagnostics | Time-domain fault Locator for RL and NEXT |
| Measurement accuracy | Exceeds TIA 1152 Level IIIe, IEC 61935 level IV |
| Measurement frequency range | 1- 2,500 MHz |